JETWELL Technology Request a quote 中文
MICROWAVE SENSOR

MP-600 Microwave Sensor Switch

Smart sensing, energy-saving and reliable; suits all kinds of lamps and automation control for a smarter, more economical life. Made in Taiwan · extra-large load · newly launched.

High-current ProAnti-interference
MP-600 Microwave Sensor

5.8GHz high-performance circuit and algorithm

With more and more sources of interference around, ordinary microwave sensors are easily disturbed and unstable. The MP-600 uses a 5.8GHz high-performance circuit and algorithm that effectively resolves interference and false triggering and delivers high reliability for demanding installations.

  • Detects people or objects in motion (no action when nothing moves).
  • Unaffected by temperature or humidity; senses through non-metallic materials such as glass and calcium silicate board.
  • Can be hidden inside a light-steel ceiling frame for easy installation and a neat look.
  • Moisture-resistant, wide voltage, adjustable settings.
Wide voltageWorks on AC100–240V
High compatibilityLED and all kinds of lamps up to 500W, or 10 low-power units
Multi-function adjustmentTime, light level and range are adjustable
Wide sensing rangeDetection range 1–10 meters
Stable and reliableUnaffected by temperature and humidity
Smart anti-interferenceMultiple units don't interfere with each other; stable in Wi-Fi environments
SPEC

Specifications

Model
MP-600
Input voltage
Wide voltage AC100–240V
Output type
Same as input voltage (power output)
Load
LED fixtures up to 500W or 10 low-power units
Resistive load (traditional incandescent lamps)
8A: AC110V/800W, AC220V/1500W
Detection angle
145°
Detection range
1–10 m (manual setting)
Dimensions
74×46×55 mm
Origin
Taiwan
  • For: bathrooms, under outdoor eaves and rain-splashed arcades; one sensing area; do not submerge.
  • On-time (5 s – 15 min) and light-sensing level are adjustable.
  • Other voltages (DC5V, 12V, 24V, AC277V) available on request.
RANGE

Detection range diagram

Dark: high-sensitivity zone; light: normal-sensitivity zone (unit: meters)
Dark: high-sensitivity zone; light: normal-sensitivity zone (unit: meters)

Settings

LIGHT (light sensing)
☼ senses all day; ☾ or other positions: no action when ambient light is above the setting; outputs power when ambient light is below the setting and movement is detected.
TIME
Sets how long power is output after sensing, from 5 seconds to 15 minutes.
Distance
Remove the screw and open the case, then adjust the blue-and-white knob inside; range 1–10 m.

⚠ Always switch off the power before opening the case, and fasten the case screw securely before powering on.

Functions and installation environment

  • The first 30 seconds after power-up is a warm-up period; the output state is undefined and may or may not switch on.
  • Power is output when movement is detected and switched off after the set time; the next detection starts only 2 seconds after the output turns off.
  • Avoid facing large metal equipment (such as elevators or pipes); the back and sides can also detect at short range.
  • When installing several sensors, keep them level, avoid facing them toward each other, and space them at least 1 m apart.
  • Indoor walls, nearby objects and obstructions affect the range; slight movement and small animals may be detected.
  • For outdoor installation, point the wires downward and fit the waterproof cover over the outside of the knob to keep it waterproof.
WIRING

MP-600 wiring

Same as the RP series: black = input (live), white = neutral, red = output (live)

Wiring diagram: RP, MP series (left) — wire the MP-600 this way
Wiring diagram: RP, MP series (left) — wire the MP-600 this way